10-13
LED display
Description
Cause
Possible solutions
PID selection
error
PID selection error.
10-00 and10-01 set to 1(AI1)
or set to 2(AI2).
When 23-05=0 and
10-33 >= 1000 or
10-
34≠1.
Check 10-00 and 10-01
Check 10-33,10-34, 23-05.
Model
selection
error
Inverter capacity setting error:
Inverter capacity setting 13-00
does not match the rated voltage.
Inverter capacity setting does
not match voltage class
(13-00).
Check inverter capacity
setting 13-00.
PI setting
error
Inverter PI setting error
Inverter pulse input selection
(03-30) selection conflicts with
PID source (10-00 and
10-01).
Check pulse input
selection (03-30) and PID
source (10-00 and 10-01).
FB (flash)
PID feedback
breaking
PID feedback signal falls below
level specified in 10-12 (PID
feedback loss detection level) for
the time specified in 10-13
(Feedback loss detection time).
Active when parameter
(10-11 = 1).
Feedback signal wire break
Feedback sensor broken.
Check feedback wiring
Replace feedback sensor.
USP (flash)
Unattended
Start
Protection
Unattended Start Protection
(USP) is enabled (enabled at
power-up.)
USP at power-up (activated
by multi-function digital input)
is enabled. The inverter will
not accept a run command.
While the warning is active
the inverter does not accept a
run command. (See
parameter 03-00 - 03-08 =
50).
Remove run command or
reset inverter via
multi-function digital input
(03-00 to 03-07 = 17) or
use the RESET key on the
keypad to reset inverter.
Activate USP input and
re-apply the power.
Fire mode
enabled
Fire mode enabled
Fire mode enabled.
Check for fire. If case of no
fire, turn off the power and
power on again.
Parameter
setting Error
Parameter setting error
The parameter setting is
incorrect.
Please refer to the manual
for correct setting