5-2
LCD Operator (Optional Keypad)
Fref Ref
12-16=005.00Hz
Monitor
12-17=000.00Hz
12-18=0000.0A
Fref Ref
12-16=005.00Hz
Monitor
12-17=005.00Hz
12-18=0001.2A
Fig 5.1: Keypad (Stopped)
Fig 5.2: Keypad (Running)
Next press the
RUN
key, see Fig 5.2. The motor should now be operating at low speed running in forward
(clockwise) direction. The parameter code 12-17 shown at the bottom left corner of the screen will change from
12-17=000.00Hz to 12-17=005.00Hz. Next press
STOP
key to stop the motor.
If the motor rotation is incorrect, power down the inverter.
After the power has been turned OFF, wait at least ten minutes until the charge indicator extinguishes
completely before touching any wiring, circuit boards or components.
Using Safety precaution, and referring to section 3.8 exchange any two of the three output leads to the motor
(U/T1, V/T2 and W/T3). After the wiring change, repeat this step
and recheck motor direction.