4-33
Group 08 Protection Parameters
Code
Parameter Name
Setting Range
Default
Unit
Control mode
Attribute
V/F SLV
PM
SLV
08-00
Stall Prevention
Function
xxx0b
:
Stall prevention is enabled in
acceleration.
0000b
-
O
O
O
xxx1b
:
Stall prevention is disabled in
acceleration.
xx0xb
:
Stall prevention is enabled in
deceleration.
xx1xb
:
Stall prevention is disabled in
deceleration.
x0xxb
:
Stall prevention is enabled in operation
x1xxb
:
Stall prevention is disabled in operation
0xxxb
:
Stall prevention in operation is based
on
deceleration time of speed-stage 1.
1xxxb
:
Stall prevention in operation is based
on
deceleration time of speed-stage 2.
08-01
Stall Prevention Level
During Acceleration
20~200
HD
:
150
ND
:
120
%
O
O
O
08-02
Stall Prevention Level
During Deceleration
200V
:
330V~410V
385V
V
O
O
O
400V
:
660V~820V
770V
08-03
Stall Prevention Level
During Run
30~200
HD
:
160
%
O
O
O
ND
:
120
08-05
Selection for Motor
Overload Protection
(OL1)
xxx0b
:
Overload Protection is disabled.
0001b
-
O
O
O
xxx1b
:
Overload Protection is enabled.
xx0xb
:
Cold Start of Motor Overload
xx1xb
:
Hot Start of Motor Overload
x0xxb
:
Standard Motor
x1xxb
:
Inverter Duty Motor
0xxxb
:
Reserved
1xxxb
:
Reserved
08-06
Start-up Mode of
Overload Protection
Operation (OL1)
0
:
Stop Output after Overload Protection
0
-
O
O
O
1
:
Continuous Operation after Overload
Protection.
08-07
Over Heat Protection
(Cooling Fan Control)
0
:
Auto (Depends on temp.)
1
-
O
O
O
1
:
Operate while in RUN Mode
2
:
Always Run
3
:
Stop Operation
08-08
Auto Voltage
Regulation (AVR)
0
:
Enable
0
-
O
O
O
1
:
Disable
08-09
Selection of Input
Phase Loss Protection
0
:
Disable
0
-
O
O
O
1
:
Enable
08-10 Selection of Output
0
:
Disable
0
-
O
O
O