4-101
02-23
Rated voltage of motor 2
Range
200V:
【
50.0~240.0
】
V
400V:
【
100.0~480.0
】
V
02-24
Rated power of motor 2
Range
【
0.01~600.00
】
KW
02-25
Rated frequency of motor 2
Range
【
4.8~599.0
】
Hz
02-26
Number of Motor Poles of Motor 2
Range
【
2~16
】
02-32
Line-to-line Resistance of motor 2
Range
【
0.001~60.000
】
Ω
02-33
Proportion of Motor Leakage Inductance
<1>
Range
【
0.1~15.0
】
%
02-15: Motor line-to-line resistance
Refer to figure 4.3.15, Y-equivalent model of an induction motor
Figure 4.3.15 Y-equivalent model an induction motor
02-19: No-load motor voltage
Parameter determines the rated flux during motor’s rated rotation in SLV control mode. Set the value of this
parameter to the same value as parameter 17-08. A value of 10~50V below the input voltage level ensures that
the motor is capable of providing adequate torque performance when operating at nominal speed (or higher
speed). Setting the value too small can result in a reduction in no-load current, weakened motor flux and an
increase in motor current while the motor is loaded.