3-33
3.18 General Specification
Item
E510
Control Mode
V/F, SLV, PMSLV control mode
Frequency
Output Frequency
0.01
~
599.00Hz
Starting Torque
150% / 1Hz (SLV mode)
,
150% / 3Hz (V/F mode)
Speed Control Range
1:50
Setting resolution
Digital input: 0.01Hz
Analog input:0.06Hz/60Hz
Setting
Keypad:
Set directly with▲▼ keys or the VR on the keypad
External Input Terminals:
AI1(0/2~10V), AI2(0/4~20mA)input
Multifunction input up/down function(Group3)
Setting frequency by communication method.
Frequency limit
Lower and upper frequency limits,
3 skip frequency settings.
Run
Operation set
Keypad run, stop button
External terminals:
Multi- operation-mode2 / 3 wire selection
Jog operation
Run signal by communication method.
Main Control
Features
V / F curve setting
15 fixed curves and one customized curve
Carrier frequency
1~16KHz (factory setting is 5kHz)
Acceleration and
deceleration control
2 Acceleration / deceleration time parameters.
4 off S curve parameters.
Multifunction input
Refer to description in group 3
Multifunction output
Refer to description in group 3
Multifunction analog output
Refer to description in group 4
Main features
Overload Detection,16 preset speeds, Auto-run, Acc/Dec
Switch (2 Stages),Main/Alt run Command select, Main/Alt
Frequency Command selection, PID control, torque boost,
V/F start Frequency, Fault reset.
Display
LED
Display: parameter / parameter value / frequency / line speed
/ DC voltage / output voltage / output current / PID feedback /
input and output terminal status / Heat sink temperature /
Program Version / Fault Log.
LED Status Indicator
Run / Stop / Forward / Reverse ,and etc.
Protective
Functions
Overload Protection (OL1)
Electrical overload protection curve
Overload Protection (OL2)
H.D mode
:
150% rated current for 1 minute.
N.D mode
:
120% rated current for 1 minute
Over voltage
200V Class
:
DC bus voltage higher than 410Vdc
400V Class
:
DC bus voltage higher than 820Vdc
Under Voltage
200V Class
:
DC bus voltage lower than 190V
400V Class
:
DC bus voltage lower than 380V
Momentary Power Loss
Restart
Inverter auto-restart after a momentary power loss.
Stall Prevention
Stall prevention for Acceleration/ Deceleration/ Operation.
Short-circuit output terminal
Electronic Circuit Protection