4-210
16-05
LCD Backlight
Range
【
0~7
】
Adjust the screen contrast of the digital operator. If set to 0 the screen backlight is turned off.
16-07
Copy Function Selection
Range
【
0
】
:
Do not copy parameter
【
1
】
:
Read inverter parameters and save to the keypad
【
2
】
:
Write the keypad parameters to inverter
【
3
】
:
Compare parameters of inverter and keypad
16-08
Selection of allowing reading
Range
【
0
】
:
Do not allow to read inverter parameters and save to the keypad
【
1
】
:
Allow to read inverter parameters and save to the keypad
LCD digital operator with built-in memory (EEPROM) can be used to store and retrieve parameters:
(1) Read: Save inverter parameters to the digital operator (IN
V → OP).
(2) Write: Write the parameters from the digital operator to the inverter and save (OP → INV).
(3) Verify: Compare the inverter parameters against the parameters in the digital operator.
16-07=0
: No action
16-07=1
: Read (all parameters are copied from the inverter to the keypad).
16-07=2
: Write (all parameter are copied from the keypad to the inverter).
16-07=3
: Verify (Compare the set value of the inverter to the parameter of the digital operator).
Set 16-08 = 0, to prevent the saved parameter data stored in the digital operator from accidentally being
overwritten.
When parameter 16-08=0 and the read operation is executed (16-07=1) a warning message of "RDP Read
Prohibited" will be displayed on the keypad and the read operation is cancelled.
For the write-in operation requires the following items to match.
(1) Inverter type
(2) Inverter rated capacity and voltage