4-208
16 LCD Function Group
Note: LCD Copy Keypad is an optional keypad for remote mounting only.
16-00
Main Screen Monitoring
Range
【
5~43
】
16-01
Sub-Screen Monitoring 1
Range
【
5~43
】
16-02
Sub-Screen Monitoring 2
Range
【
5~43
】
At power-up the inverter shows two monitor sections on the display, main monitor section consisting of one
monitor (large font) and a sub-screen monitor section consisting of two monitors (smaller font).
Choose the monitor signal to be displayed on the main-screen monitor screen using parameter 16-00, and the
monitor signals to be displayed on the sub-screen monitor with parameters 16-01 and 16-02, similar to monitor
parameters 12-5 ~ 12-43.
16- 03
Display unit
Range
【
0
】
:
Frequency display unit is Hz (Resolution is 0.01Hz)
【
1
】
:
Frequency display unit is % (Resolution is 0.01%)
【
2
】
:
Frequency display unit is rpm
【
3~39
】
:
Reverse
【
40~9999
】
:
100% is XXXX with no decimals (integer only)
【
10001~19999
】
:
100% is XXX.X with 1 decimal
【
20001~29999
】
:
100% is XX.XX with 2 decimals
【
30001~39999
】
:
100% is X.XXX with 3 decimals
16- 04
Engineering Unit
Range
【
0
】
:
No Unit
【
1
】
:
FPM
【
2
】
:
CFM
【
3
】
:
PSI
【
4
】
:
GPH
【
5
】
:
GPM
【
6
】
:
IN
【
7
】
:
FT
【
8
】
:
/s
【
9
】
:
/m
【
10
】
:
/h
【
11
】
:
°F
【
12
】
:
inW
【
13
】
:
HP
【
14
】
:
m/s
【
15
】
:
MPM
【
16
】
:
CMM
【
17
】
:
W
【
18
】
:
KW
【
19
】
:
m
【
20
】
:
°C
【
21
】
:
RPM
【
22
】
:
Bar
【
23
】
:
Pa
16-03:
Display unit of digital operator
Set the units of the following items to be displayed, the frequency reference (05-01, 00-18, 06-01~06-15) and the
monitoring frequency 12-16, 12-17 (Output frequency)
16-04:
Display unit of engineering
When 16-03 = 00040-39999, engineering units are enabled. The displayed set range and the frequency range of
unit (05-01, 06-01~06-15) as well as the monitoring frequency (12-16, 12-17) are changed by parameters 16-04
and 16-03.