4-113
03-0X =17:
Fault reset
When the inverter trips on a fault the fault output contact is activated, the inverter output is turned off (base block)
and the keypad displays a dedicated fault message.
The following options are available to reset a fault:
1. Program one of the multi-function digital inputs (03-00 to 03-05) to 17 (reset fault) and activate input.
*
2. Press the reset key of the digital operator (RESET).
*
3. Cycle power to the inverter.
Important Note:
If a run command is active during power-up, the inverter will
start running automatically.
*
To reset an active fault the run command has to be removed.
03-0X =18:
Auto run mode enable
When active auto run mode function is enabled, please refer to group 06 for more information.
03-0X =19:
Speed Search 1 (from the maximum frequency).
03-0X =34:
Speed Search 2 (from the frequency command).
Refer to the "speed search" function.
03-0X =20:
Energy saving enabled
Manual energy savings function is set with parameters 11-12 and 11-18.
For the manual energy saving operation refer to Figure 4.3.88.
03-0X =21:
PID integral reset
03-0X =22:
Counter Input 1
When input goes from OFF to ON the counter value
increased by ‘1’,
2ms
The width of the
trigger signal should
be large than 2ms
C0001
C0002
C0003
C0004
C0005
C0001
C0002
Single preset
count 1 set by
Parameter 03-22
03-22=5
Count display set
by 12-00=00008
Count input Multi-
function input
03-0X =23:
Counter Reset
When active counter is reset to 0 and the inverter display shows
“C0000”. Deactivate the counter reset input to
enable counter.