4-154
07-09 =3: Coast to stop with timer
When a stop command is issued the motor will coast to a stop after the minimum Baseblock time (07-18) has
expired and the inverter ignores the run command until the timer has expired.
The total time of the timer is determined by the deceleration time (00-15, 17, 22 or 24) and the output frequency
upon stop, refer to figure 4.3.61 for details.
Output
Frequency
Run
Time
Time
Stop
10%
100%
Maximum output frequency
(Fmax, 01- 02)
Output
frequency
upon stop
command
T1
T1
:
Total time
T1
Deceleration
time
(eg. 00- 15)
Minimum
baseblock
time tb.b
(07-18)
Run
Run
Stop
Figure 4.3.61 Coast to stop with timer
07-10
Speed Search Mode Selection
Range
【
0
】
: Disabled
【
1
】
: Execute speed search once
【
2
】
: Speed Search Start
07-10 = 0:
Speed search is disabled and the inverter output frequency starts from min. frequency (01-08).
07-10 = 1:
Speed search is enabled and activated only once after power-up and first run command.
07-10 = 2:
Speed search is enabled and activated after every run command
Note:
Speed search function is unavailable for inverter size 1 and 2 and control mode set to PMSLV (00-00=5).
07-13
Low voltage detection level
Range
【
200V Class
:
150~300V
】
【
400V Class
:
250~600V
】
07-25
Low voltage detection time
Range
【
0.00~1.00
】
Sec
Parameter 07-13 low voltage detection level can be adjusted from 150 to 300 Vdc (200V class) or 250 to 600 Vdc
(400V class).