3-14
3.6 Wire Gauges, Tightening Torque, Terminal , Short Circuit, Circuit Breaker and Fuse Ratings
Wire Gauges
TM1
Frame
size
HP
Power
specification
Voltage
Amps
Input wiring
(TM1)
Output wiring
(TM1)
Tightening Torque
kgf.cm
lbf.in
Nm
Frame1
0.5/1
200V
~
240V
600
20
14 AWG
(2.5 mm²)
14 AWG
(2.5 mm²)
9.8
8.5
0.96
1/2
380V
~
480V
14
– 12 AWG
(2.5
– 4.0 mm²)
14
– 12 AWG
(2.5
– 4.0 mm²)
Frame2
2(-H)/3/5
200V
~
240V
600
45
14
– 8 AWG
(2.5
– 10 mm²)
14
– 8 AWG
(2.5
– 10 mm²)
18.4
15.9
1.8
3/5
380V
~
480V
14
– 8 AWG
(2.5
– 10 mm²)
14
– 8 AWG
(2.5
– 10 mm²)
Frame 3/4
7.5/10/15/2
0
200V
~
240V
600
100
12
– 6 AWG
(4.0
– 16 mm²)
12
– 6 AWG
(4.0
– 16 mm²)
24.5
21.2
2.4
7.5/10/15/2
0/25
380V
~
480V
600
65
8 AWG
(10 mm²)
8 AWG
(10 mm²)
Frame 5
25
200V
~
240V
600
100
6 AWG
(16 mm²)
6 AWG
(16 mm²)
30
26
2.9
30
380V
~
480V
600
75
6 AWG
(16 mm²)
6 AWG
(16 mm²)
Frame 6
30/40
200V
~
240V
600
175
0 AWG
(50 mm²)
0 AWG
(50 mm²)
81.7
70.7
8
40/50/60/75
380V
~
480V
600
0 AWG
(50 mm²)
0 AWG
(50 mm²)
TM2
Frame
size
Horsepower
Power specification
Terminal Wiring Size
(TM2)
Tightening Torque
kgf.cm
lbf.in
Nm
Frame1
0.5/1
200V
~
240V
26~18 AWG (0.5~1.5 mm²)
5.7
5
0.56
1/2
380V
~
480V
Frame2
2(-H)/3/5
200V
~
240V
3/5
380V
~
480V
Frame 3/4
7.5/10/15/20
200V
~
240V
7.5/10/15/20/25
380V
~
480V
Frame 5
25
200V
~
240V
16 AWG (0.5~1.5 mm²)
8
7
0.79
30
380V
~
480V
Frame 6
30/40
200V
~
240V
14 AWG (0.5~1.5mm²)
8
7
0.79
40/50/60/75
380V
~
480V
NOTES:
* Wire size shown is based on maximum terminal size. Please consult the NEC or local codes for proper size to be used.
* Use only copper wires. Proper diameter wire should be based on ratings at 75°C.
* For safety reasons do not use under sized wiring.