4-31
Group 07 Start/Stop Parameters
Code
Parameter Name
Setting Range
Default
Unit
Control mode
Attribute
V/F
SLV
PM
SLV
07-00
Momentary Power Loss and
Restart
0
:
Disable
0
-
O
O
X
1
:
Enable
07-01
Fault Reset Time
0~7200
0
s
O
O
O
07-02
Number of Auto Restart
Attempts
0~10
0
-
O
O
O
07-03
Reset Mode Setting
0
:
Enable Reset Only when Run
Command is Off
1
:
Enable Reset when Run
Command is On or Off
07-04
Momentary Power Loss and
Restart
0
:
Enable Direct run on power up
1
-
O
O
O
1
:
Disable Direct run on power up
07-05
Delay-ON Timer
1.0~300.0
1.0
s
O
O
O
07-06
DC Injection Braking Start
Frequency
0.0~10.0
1.5
Hz
O
O
O
07-07
DC Injection Braking Level
(Current Mode)
0~100
50
%
O
O
O
07-08
DC Injection Braking Time
0.00~100.00
0.50
s
O
O
O
07-09
Stop Mode Selection
0
:
Deceleration to Stop
0
-
O
O
O
1
:
Coast to Stop
2
:
DC Braking Stop in All Fields
3
:
Coast to Stop with Timer
07-10
Speed Search Mode
Selection
0
:
Normal Start
O
O
O
1
:
Execute Speed Search Once
2
:
Speed Search Start
07-13
Low Voltage Detection Level
200V
:
150~300
190
V
O
O
O
400V
:
250~600
380
07-15
DC Injection Brake Mode
0
:
Voltage Mode
1
:
Current Mode
1
O
O
X
07-16
DC Injection Braking Time at
Start
0.00~100.00
0.00
s
O
O
O
07-18
Minimum Base block Time
0.1~5.0
-
Sec
O
O
O
07-19
Speed Direction Search
Operation Current
0~100
50
%
O
O
X
07-20
Speed Search Operating
Current
0~100
20
%
O
O
X
07-21
Integral Time of Speed
Searching
0.1~10.0
2.0
Sec
O
O
X
07-22
Delay Time of Speed
Searching
0.0~20.0
0.2
Sec
O
O
X
07-23
Voltage Recovery Time
0.1~5.0
2.0
Sec
O
O
X
07-24
Direction-Detection Speed
Search Selection
0
:
Invalid
1
-
O
O
X
1
:
Valid