4-48
Group 16 LCD Function Parameters
Code
Parameters
Setting Range
Default
Unit
Control Mode
Attribute
V/F
SLV
PM
SLV
16-00
Main Screen
Monitoring
5~39
when using LCD to operate, the monitored item
displays in the first line. (default is frequency
command)
16
-
O
O
O
*1
16-01
Sub-Screen
Monitoring 1
5~39
when using LCD to operate, the monitored item
displays in the second line. (default is output
frequency)
17
-
O
O
O
*1
16-02
Sub-Screen
Monitoring 2
5~39
when using LCD to operate, the monitored item
displays in the third line. (default is output
current))
18
-
O
O
O
*1
16-03 Display Unit
0~39999
Determine the display way and unit of
frequency command
0
-
O
O
O
0
:
Frequency display unit is 0.01Hz
1
:
Frequency display unit is 0.01%
2
:
Frequency display unit is rpm.
3~39
:
Reserved
40~9999
:
Users specify the format, Input 0XXXX
represents the display of XXXX at 100%.
10001~19999
:
Users specify the format; Input 1XXXX
represents the display of XXX.X at 100%.
20001~29999
:
Users specify the format, Input 2XXXX
represents the display of XX.XX at 100%.
30001~39999
:
Users specify the format, Input 3XXXX
represents the display of X.XXX at 100%.
16-04
Engineering
Unit
0
:
Without using engineering units
0
-
O
O
O
1
:
FPM
2
:
CFM
3
:
PSI
4
:
GPH