7-2
7.2 Run/Stop from External Switch / Contact or Pushbutton (00-02=1)
Use an external contact or switch to Run and Stop the inverter.
Set parameter 00-04 to 0 for 2-wire operation, multi-function input terminal S1 is set to run operation forward
command.
00-02 Run Command Selection = 1
Permanent Switch / Contact
Set jumper JP1
to position1 & 2
JP1
1
2
3
NPN
PNP
AO
S6
S(+)
S(-)
AGND
10V
SG
COM
S2
S4
SF1
Start / Stop Switch
(Maintained)
Forward
Command/FWD
Digital Input
Common
Control Terminals /
User Terminals
24V
AI1
R2A
R2B
R1C
S1
S3
S5
AI2
R1A
R1B