4-189
Actual jump width
Jump 1
Jump 2
Output
Frequency
Frequency
Reference
Figure 4.3.87 Jump frequency overlap
11-12
Manual Energy Saving Gain (VF)
Range
【
0~100
】
%
11-18
Manual Energy Saving Frequency
Range
【
0.0~599.0
】
Hz
Manual energy savings reduces the output voltage for the purpose of saving energy.
To enable manual energy savings set one of the multi-function digital input (03-00 to 03-05) to 20 and activate the
input or use parameter 11-18 to set the manual energy savings activation frequency.
When the output frequency rises above the value set in parameter 11-18 manual energy savings function is
enabled. Setting parameter 11-18 manual energy savings frequency to 0.0 Hz disables the manual energy
savings frequency activation function. Refer to Figure 4.3.88 for more information.
Note:
Only use manual energy savings functions in combination with light loads.
Manual energy saving gain (11-12) determines the output voltage of the inverter when manual energy savings is
enabled. Output voltage is percentage gain times the V/F voltage.
Manual energy saving control uses the voltage recovery time (07-23) to change the output voltage, refer to figure
4.3.88.
Run command
Manual energy
saving command
Output frequency
Output voltage
ON
ON
OFF
OFF
Frequency reference
≥
11-18
V/F pattern (01-02 to 01-09) x 11-12
Voltage change rated = 07-23 (voltage recovery time)
Figure 4.3.88 Manual energy saving operation