4-66
Multi-function digital input terminals (03-00 ~ 03-05) set to 14: When the emergency stop input is activated the
inverter will decelerate to a stop using the time set in parameter 00-26.
Note:
After an emergency stop command the run command and emergency stop command have to be removed
before the inverter can be restarted. Please refer to Figure 4.3.9. The emergency stop function can be used to
stop inverter in case of an external event.
Multi-function digital input terminals (03-00 ~ 03-05) set to 15: When the base block input is activated the inverter
output will turn off and the motor will coast to a stop.
00-27
HD/ND Mode
Range
【
0
】
: HD (Heavy Duty / Constant Torque)
【
1
】
: ND (Normal Duty / Variable Torque)
The inverter overload curve, carrier frequency, stall prevention level, rated input/output current and maximum
frequency are automatically set based on the inverter duty (HD/ND) selection.
Please refer to table 4.3.2 for detailed information
Table 4.3.2 Heavy Duty (Constant torque) / Normal Duty (Variable torque)
00-27
Overload
capacity
Carrier
frequency
Maximum
output
frequency
Stall
prevention
level
Rated input /
output current
0
(Heavy Duty)
150%, 1min
2-16KHz
(KVA dependent)
599.00Hz
150%
(08-00, 08-01)
Refer to section
3.15
1
(Normal Duty)
120%, 1min
2-16KHz
(KVA dependent)
120.00Hz
120%
(08-00, 08-01)
Note:
Dual rating only can be used for 200V Class 25HP and above and 3400V class 30HP and above.
Select V/F curve (Group 1) and enter motor data (Group 2) to match your application. In Heavy Duty mode the
maximum output frequency is 599Hz for all control modes, except for SLV mode (Sensorless Vector / Open Loop
Vector Mode) where the maximum output frequency is limited based on the inverter rating, see table below.
Horsepower
Carrier Frequency Limit
Maximum
output
frequency
220V 1~10HP, 440V 1~15HP
-
150Hz
220V 15~25HP, 440V 20HP
-
110Hz
440V 25~30HP
-
100Hz
220V 30~40HP, 440V 40~75HP,
11-01 set 8KHz or below
100Hz
220V 30~40HP, 440V 40~75HP,
11-01 set 8KHz or higher
80Hz
Note:
Normal duty mode only available in V/F mode. All other modes must use the Heavy Duty setting.