4-127
Function
Frequency Detection Function
Description
Frequency
agree
time
time
ON
OFF
FWD
REV
03-14
03-14
Freq
Reference
Output
Frequency
Frequency
Agree
Signal
ON
Freq
Reference
Output is active when the output frequency
falls within the frequency reference minus
the frequency detection width (03-14).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 2 (Frequency
agree).
Set
frequency
agree
time
time
ON
OFF
FWD
REV
03-14
Output
Frequency
Setting
Frequency
Agree
Signal
ON
03-13
03-13
03-14
Output is active the output frequency falls
within the frequency detection width (03-14)
of the set frequency detection level (03-13).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 3 (Set
frequency agree).
Output
frequency
detection 1
ON
ON
OFF
OFF
03-14
03-14
03-13
03-13
03-13
03-13
time
time
Output
Frequency
Output
Frequency
Detection 1
Signal
Output is active when the output frequency
rises above the frequency detection level
(03-13) + frequency detection width (o3-14)
and deactivates when the output frequency
falls below frequency detection level
(03-13).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 4 (Output
frequency detection 1).
Output
frequency
detection 2
Output is active when the output frequency
is below the frequency detection level
(03-13) + frequency detection width (03-14)
and turns off when the output frequency
falls below frequency detection level.
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 5 (Output
frequency detection 2).
Frequency
Output
DC Brake
DC Brake
ON
ON
OFF
OFF
Output
Frequency
Frequency
Output
Ing
OFF
OFF
OFF
OFF
OFF
ON
ON
Run
command
Base
Block
Output is active when the inverter output
frequency is greater than 0.
OFF
OFF
ON
ON
03-14
03-14
03-13
03-13
03-13
03-13
time
time
Output
Frequency
Output
Frequency
Detection 2
Signal
ON