4-60
00-03=3:
PLC control
The inverter is controlled by the inverter built-in PLC logic. Refer to section 4.4.
00-04
Operation Modes for External Terminals
Range
【
0
】
: Forward/Stop-Reverse/Stop
【
1
】
: Run/Stop- Reverse/ Forward
【
2
】
: 3 Wire Control Mode - Run/Stop
00-04 is valid when run command is set to external mode by 00-02/00-03 =1.
2 Wire Operation Mode
,
Set 00-04=
【
0/1
】
first, before setting (03-00, 03-04) to
【
0
】
or
【
1
】
00-04=
【
0
】
, Set external terminals (03-00 to 03-05) function to 0 for FWD/Stop or Set to 1 for REV/Stop..
00-04=
【
1
】
, Set external terminals (03-00 to 03-05) function to 0 for Run/Stop or Set to 1 for FWD/REV
3 Wire Operation Mode,
00-04 =
【
2
】
Terminals S1, S2, S3 are used in a combination to enable 3 wire run/stop mode.
Settings for 03-00, 03-01, and 03
–02 will not be effective... (Refer to group 03)
00-05
Main Frequency Command Source Selection
00-06
Alternative Frequency Source Selection
Range
【
0
】
: Up/Down on Keypad
【
1
】
: Potentiometer on Keypad
【
2
】
: External AI1 Analog Signal Input
【
3
】
: External AI2 Analog Signal Input
【
4
】
: External Up/Down Frequency Control
【
5
】
: Communication Setting Frequency
【
6
】
: Reserved
【
7
】
: Pulse Input
00-05/00-06= 0:
Keypad
Use the keypad to enter the frequency reference or by setting parameter 05-01 (frequency reference 1). Note that
once the frequency command is switched to alternative frequency reference and 00-06 is set to 0, the frequency
can be adjusted using parameter 05-01.
00-05/00-06= 1:
Potentiometer on Keypad
Use the keypad potentiometer to set frequency reference
00-05/00-06= 2, 3:
External Analog Input AI1 / External Analog Input AI2
Set any of the multi-function terminals (03-00~03-05) to 13, to switch between main and alternate frequency.
Use analog reference from analog input AI1 or AI2 to set the frequency reference (as shown in Figure 4.3.4).
Refer to parameter 04-00 to select the signal type.
04-00
Analog Input Signal Type Select
(AI1/AI2)
AI1 AI2
(0): 0~10V (0~20mA) 0~10V (0~20mA)
(1): 0~10V (0~20mA) 2~10V (4~20mA)
Factory Default
(2): 2~10V (4~20mA) 0~10V (0~20mA)
(3): 2~10V (4~20mA) 2~10V (4~20mA)