4-214
17 Automatic Tuning Parameters
17-00
Mode selection of automatic tuning
Range
【
0
】
: Rotational auto-tuning
【
1
】
: Static auto-tuning
【
2
】
: Stator resistance measurement
【
3
】
: Reserved
【
4
】
: Loop tuning
【
5
】
: Rotational Auto-tuning Combination (Item: 4+2+0)
【
6
】
: Static Auto-tuning Combination (Item: 4+2+1)
17-01
Motor rated output power
Range
【
0.00~600.00
】
KW
17-02
Motor rated current
Range
VF mode : 10%~120% of the inverter rated current
SLV mode : 25%~120% of the inverter rated current
17-03
Motor rated voltage
Range
200V:
【
50.0~240.0
】
V
400V:
【
100.0~480.0
】
V
17-04
Motor rated frequency
Range
【
5.0~599.00
】
Hz
17-05
Motor rated speed
Range
【
0~24000
】
rpm
17-06
Pole number of motor
Range
【
2~16
】
pole
17-08
Motor no-load voltage
Range
200V:
【
50~240
】
V
400V:
【
100~480
】
V
17-09
Motor excitation current
Range
【
15~70
】
% of motor rated current
17-10
Automatic tuning start
Range
【
0
】
:
Disabled
【
1
】
:
Enabled
17-12
Proportion of Motor Leakage Inductance
Range
【
0.1~15.0
】
%
17-13
Motor Slip Frequency
Range
【
0.10~20.00
】
Hz
17-14
Rotational Auto-tuning
Range
【
0
】
:
V/F type rotational auto-tuning
【
1
】
:
Vector type rotational auto-tuning
*1. Values of motor rated voltage are for 200V class, double the values for 400V class.
*2. The setting range of motor rated frequency is 0.0 to 400.0 Hz in HD Mode (00-27=0), 0.0 to 120.0 Hz in
ND Mode (00-27=1) and 0.0 to 599.0 Hz in high frequency mode.