Group 09 Communication Parameters
Code
Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
SLV
PM
SLV
09-00
INV Communication
Station Address
1~32
1
-
O
O
O
*3
09-01
Communication Mode
Selection
0
:
MODBUS
0
O
O
O
*3
*5
1
:
BACnet
2
:
Reserved
3
:
Reserved
4
:
Reserved
09-02
Baud Rate Setting
(bps)
2
:
4800
4
-
O
O
O
*3
3
:
9600
4
:
19200
5
:
38400
09-03 Stop Bit Selection
0
:
1 Stop Bit
0
-
O
O
O
*3
1
:
2 Stop Bit
09-04 Parity Selection
0
:
No Parity
0
-
O
O
O
*3
1
:
Even Bit
2
:
Odd Bit
09-05
Communication Data
Bit Selection
0
:
8 Bit Data
0
-
O
O
O
*3
1
:
7 Bit Data
09-06
Communication Error
Detection Time
0.0~25.5
0.0
S
O
O
O
*3
09-07 Fault Stop Selection
0
:
Deceleration to Stop By Deceleration Time 1
3
-
O
O
O
*3
1: Coast to Stop
2: Deceleration to Stop By Deceleration Time 2
3: Continue
09-08
Comm. Fault
Tolerance Count
1~20
1
-
O
O
O
*3
09-09 Waiting Time
5~65
5
ms
O
O
O
*3
09-10
BACNET Device
Instance Number
1~254
1
O
O
O
*3
:
Parameter group 09 settings are NOT set to factory default when inverter is initialized (13-08).
Note:
Changes to group 09 require the power to be cycled to take effect.