4-111
03-0X =10:
Acceleration/deceleration 1 selection
03-0X =30:
Acceleration/deceleration 2 selection
Refer to the "multi-function digital input terminals select ac
celeration / deceleration time”
03-0X =11:
Inhibit Acceleration/deceleration command (hold command)
When activated suspends the acceleration / deceleration operation and maintains the output frequency at current
level.
Operation of inhibit Acceleration/deceleration function, please refer figure 4.3.21.
The frequency reference value is saved when the acceleration/deceleration inhibit command is active and the
frequency reference value is saved even when powering down the inverter.
Power
Supply
Forward
Run
Inhibit
Acc/Dec
Command
Frequency
Reference
Output
Frequency
ON
ON
OFF
ON
OFF
ON
OFF ON
OFF
ON
Hold
Hold
time
time
time
time
time
Figure 4.3.21 Inhibit acceleration / deceleration command operation
03-0X =12:
Main / Alternative Run Switch Function
When active, run command source is set to the alternative run command (00-03).
Note:
Digital input function 27 (Local/ Remote control selection) has a higher priority than the main/alternative run
switch.
03-0X =13:
Main/ Alternative Frequency Switch Function
When active, frequency command source is set to the alternative frequency command (00-06). When PID
function is active (10-03=XXX1B), this function is disabled and the frequency reference is set by the PID function.
Note:
Digital input function 27 (Local/ Remote control selection) has a higher priority than the main/alternative run
switch.