4-116
03-0X =27: Local / Remote selection.
Switch the inverter frequency reference source between Local (keypad) or Remote (control circuit terminals or
RS485). Use parameter 00-05 (Main frequency command source selection) and 00-02 (Run command selection)
to select the remote source.
Note:
In 3-wire operation terminal S1 and S2 are reserved for run/stop operation and the Local / Remote function
can only be set to digital input terminals S3 to S6 (03-02 to 03-05).
Note:
To switch between local and remote the inverter has to be stopped.
Input
Mode
Frequency Reference / Run/Stop Command Source
ON
Local
- Frequency reference and Run-Stop from keypad.
- LEDs SEQ and REF are off.
OFF
Remote
- Frequency reference source selected by parameter 00-05 and
Run-Stop source selected by parameter 00-02.
- LEDs SEQ and REF are on.
03-0X =28:
Local/Remote selection
Switch between terminal source and communication (RS-422/RS-485) source for frequency reference and
operation command.
In Remote mode, indicators of SEQ and REF are on; you can use terminals AI1 and AI2 to control the frequency
command, and use terminals S1, S2 or communication terminal RS-485 to control the operation command.
Input
Mode
Frequency Reference / Run/Stop Command Source
ON
Communication
- Frequency reference and run/stop command control via communication
(RS-422/RS-485).
OFF
Terminal
- Frequency reference source from AI1 / AI2 input (00-05=1) and
Run-Stop command from terminals S1 / S2 (00-02=1).
Figure 4.3.23 Remote mode operation selection
03-0X =29:
Jog Frequency Selection
When jog frequency selection is on, the inverter will depend on the parameter 00-18 (jog frequency) as the
command.
Keypad
Frequency Reference
and
Run Command
RS-422/RS-485
communications
Control circuit
terminals
ON
OFF
ON
OFF
Set one of 03-00 to 03-07 = 27
Remote Mode
Set one of 03-00 to 03-07 = 28
Local Mode