4-62
S3
GND
0V
Serial pulse input
(Input resistance : 3.89 K
Ω )
Specifications
Low Input Level
:
0.0 to 0.5 V
High Input Level
:
4.0 to 13.5 V
Duty cycle: (ON / OFF) 30 % to 70%
Pulse Input Frequency Range: 50 to 25 KHz
Figure 4.3.5 Frequency reference from pulse input
00-07
Main and Alternative Frequency Command Modes
Range
【
0
】
: Main reference frequency
【
1
】
: Main fre alternative frequency
When set to 0 the reference frequency is set by the main reference frequency selection of parameter 00-05.
When set to 1 the reference frequency is sum of the main reference frequency (00-05) and alternative frequency
(00-06).
Note:
The inverter will display the SE1 error when 00-07 = 1 and parameter 00-05 and 00-06 are set to the same
selection.
When parameter 00-06 is set to 0 (Keypad) the alternative frequency reference is set by parameter 05-01
(Frequency setting of speed-stage 0).
00-08
Communication Frequency Command
– READ ONLY
Range
【
0.00~599.00
】
Hz
Display the frequency reference when 00-05 or 00-06 is set to communication control (3).
00-09
Communication Frequency Command Memory
Range
【
0
】
: Do not store the communication frequency command at power down
【
1
】
: Store communication frequency reference at power down
Note:
This parameter is only effective when frequency reference is set via communication (00-05 / 00-06 = 3).
00-10
Initial Frequency Selection
Range
【
0
】
: By Current Freq Command
【
1
】
: By Zero Freq Command
【
2
】
: By 00-11
00-11
Initial Frequency Setpoint
Range
【
0.00~599.00
】
Hz
Notes:
- This parameter is only effective in keypad mode
- When 00-10=
【
0
】
, the initial frequency will be current frequency.
- When 00-10=
【
1
】
, the initial frequency will be 0.
- When 00-10=
【
2
】
, the initial frequency is set by parameter 00-11.