8-6
8.6 Analog Output Setup
Signal:
Use parameter 04-11 to select the analog output signal for AO.
Gain:
Use parameter 04-12 to adjust the gain for AO. Adjust the gain so that the analog output (10V) matches
100% of the selected analog output signal (04-11). Use parameter 04-15 to set slope direction.
Bias:
Use parameter 04-13 to adjust the bias for AO. Adjust the bias so that the analog output (0V) matches 0%
of the selected analog output signal (04-11).
Example: Analog Output Wiring
AO
24V
AI1
S6
S(+)
S(-)
AGND
10V
R2A
R2B
R1C
S1
S3
S5
AI2
R1A
SG
COM
S2
S4
SF1
R1B
Analog
Common
Control Terminals /
User Terminals
Analog
Output
+
-
Example:
Set 04-11 as required according to the table below.
0
10V
Xmax
A
Xmax( 04-11)
Xmax/2
5 V
04-12
AO Gain
Range
【
0 ~ 1000.0
】
%
04-13
AO Bias
Range
【
-100.0 ~ 100.0
】
%
04-15
AO Slope
Range
【
0
】
: Positive
【
1
】
: Negative
Note:
The max output voltage is 10Vdc limited by the inverter hardware. Use external devices that require a
maximum of 10Vdc signal.
04-11
A
Xmax
【
0
】
Output frequency
upper frequency limit
【
1
】
Frequency Setting
upper frequency limit
【
2
】
Output voltage
Motor Rated Voltage
【
3
】
DC Bus Voltage
220V: 0~400V
440V: 0~800V
【
4
】
Output current
rated current of
inverter