4-231
22-06: PM motor rated frequency
Set the motor rated frequency according to the motor nameplate.
Only one of the two values is required, either PM motor rated speed (22-04) or PM motor rated frequency (22-06),
the inverter will automatically calculate the other upon entering the data based on the formula below:
120 x f (PM motor rated frequency
(PM motor rated speed) N =
P (PM motor pole number)
22-10
PM SLV Start Current
Range
【
20.0 ~ 120.0
】
% (Motor Rated Current)
22-11
I/F Mode Start Frequency Switching Point
Range
【
1.0 ~ 20.0
】
%
22-14
Armature Resistance of PM Motor
Range
【
0.001 ~ 30.000
】
Ω
22-15
D-axis Inductance of PM Motor
Range
【
0.01 ~ 300.00
】
mH
22-16
Q-axis Inductance of PM Motor
Range
【
0.01 ~ 300.00
】
mH
22-18
Flux-Weakening Limit
Range
【
0 ~ 100
】
%
22-21
PM motor tuning
Range
【
0
】
: PM Motor Tuning is not Active
【
1
】
: Parameter Auto-tune (for PMSLV Tuning)
22-23
PM SLV acceleration time
Range
【
0.1~10.00
】
Sec
22-10: PMSLV Start Current
Set the torque current at start up as % of motor rated current.
22-11: I/F Mode Start Frequency Switching Point
Function for the switching from open-loop to closed-loop in PMSLV mode. The unit is percentage of rated speed
of the motor. It recommended setting this parameters to a value greater than 5% for 400V and a value greater
than 10% for 200V.
22-14: Armature Resistance of PM Motor
Set resistor for each phase of the motor in increments
of 0.001Ω. Value is set automatically during motor tuning
(22-21).
22-15: D-axis Inductance of PM Motor
Set motor D-axis inductance in increments of 0.001mH. Value is set automatically during motor tuning (22-21).