4-203
13-08=3: 2 Wire Initialization (230V/400V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to figure 4.3.1. Inverter input voltage (01-14) is automatically set to 220V (220V
class) or 400V (440V class). When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=4: 2 Wire Initialization (230V/460V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to figure 4.3.1. Inverter input voltage (01-14) is automatically set to 220V (220V
class) or 460V (440V class). When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=5: 2 Wire Initialization (220V /415V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to figure 4.3.1. Inverter input voltage (01-14) is automatically set to 220V (220V
class) or 415V (440V class). When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=6: 2 Wire Initialization (230V/400V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to figure 4.3.1. Inverter input voltage (01-14) is automatically set to 230V (220V
class) or 400V (440V class). When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=7: 2 Wire Initialization (220V/440V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to figure 4.3.1. Inverter input voltage (01-14) is automatically set to 220V (220V
class) or 440V (440V class). When 01-00 (V/F curve) = F, 01-02 will automatically set to 50Hz.
13-08=8: 2 Wire Initialization (220V/440V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to figure 4.3.1. Inverter input voltage (01-14) is automatically set to 220V (220V
class) or 440V (440V class). When 01-00 (V/F curve) = F, 01-02 will automatically set to 60Hz.
13-08=1112: PLC Initialization
Clear built-in PLC ladder logic and related values.
The following parameters are not affected parameter 13-08 Restore to Factory / Initialization
No.
parameters
00-00
Control Mode Selection
00-34
Language
00-27
HD/ND Mode Selection
***
01-00
V/F Curve Selection
01-26
V/F Curve Selection of Motor 2
13-00
Inverter Capacity Selection
13-03
Cumulative Operation Hours 1
13-04
Cumulative Operation Hours 2
13-05
Selection of Cumulative Operation Time