4-198
12 Monitoring Parameters
12-00
Display Screen Selection (LED)
Range
0 0 0 0 0
MSD LSD
00000~88888 Each digit can be set from 0 to 8 as listed below.
【
0
】
: No display
【
1
】
: Output current
【
2
】
: No display
【
3
】
: DC bus voltage
【
4
】
: heatsink temperature
【
5
】
: PID feedback
【
6
】
: AI1 value
【
7
】
: AI2 value
【
8
】
: Counter
Note:
The highest bit is used for power-up monitor. The 4 least significant bits can be used to customize the
display sequence see chapter 4.1.4.
12-01
PID Feedback Display Mode (LED)
Range
【
0
】
:
Display the feedback value as integer (xxx)
【
1
】
:
Display the feedback value with one decimal (xx.x)
【
2
】
:
Display the feedback value (x.xx) with two decimals
12-02
PID Feedback Display Unit Setting (LED)
Range
【
0
】
:
xxxxx (no unit)
【
1
】
:
xxxPb (pressure)
【
2
】
:
xxxFL (flow)
12-03
Line Speed Display (LED)
Range
【
0~60000
】
RPM
Set motor rated RPM for the inverter to display the actual motor speed based on the output frequency.
Motor synchronous speed = 120 x Rated frequency ÷ Number of poles.
12- 04
Line Speed Display Mode (LED)
Range
【
0
】
: Display Inverter Output Frequency
【
1
】
: Line Speed Display at Integer. (xxxxx)
【
2
】
: Line Speed Display at One Decimal Place. (xxxx.x)
【
3
】
: Line Speed Display at Two Decimal Places. (xxx.xx)
【
4
】
: Line Speed Display at Three Decimal Places. (xx.xxx)
12-
04≠0,
line speed is always displayed in run or stop mode. Set 12-03 to the maximum line speed that
corresponds to the maximum output frequency.
Example:
Line speed display 12-03 is 1800, the keypad display will show 900 when the output frequency is 30Hz.