58/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
5 General functions, fundamentals
01.03.2005
5
General functions, fundamentals
5.1 Time
switch
A time switch is available for the heating circuit. In “Automatic” mode, the heating cir-
cuit, operates according to that time switch. A switching program can be defined for
each day of week.
Using the program entered, the time switch controls the change of operating modes
and the associated setpoints.
Operation of the time switch is described in Operating Instructions B3131.
5.1.1 Communication
If the controller is connected to other controllers via communication, the time switch can
be provided to other controllers, or the time switch of some other controller can be
used.
Following combinations are possible:
Entry Effect
Diagram
Autono-
mous
Time switch only acts locally on this controller.
It has no impact on other controllers on the
bus.
Slave
The time switch in this controller is not active.
The time switch acting is the external time
switch acting in the geographical zone set on
this controller as the time switch receiving
zone. The external time switch must be set as
the time switch master.
Master
The time switch in this controller is active.
The time switch also acts on all other control-
lers where the time switch is switched off (time
switch slave) and which have the geographical
zone of this controller set as the time switch
receiving zone.
31
4
0Z
0
8
Main menu > Commissioning > Communication > Room Heating circuit
Operating line
Range
Factory setting
Geographical zone (apartment)
1…126 1
Time switch operation
Autonomous / Slave /
Master
Autonomous
Time switch slave (apartment)
1…126 1
5.1.2
Time switch for external controllers on the bus
The time switch can also be provided to external controllers on the bus.
If the RMK770 is not connected to a heating circuit, the time switch will automatically be
hidden. But if required, this time switch can be used for external controllers on the bus
(e.g. for RXB… room controllers).
For that purpose, the hidden time switch must be activated.