53/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
4 General settings
01.03.2005
4 General
settings
4.1
Time of day and date
4.1.1 Operating
principle
The controller has a yearly clock with time of day, weekday and date.
The following time formats are available:
Time format
Date
Example
Time of day
Example
24 hours
dd.mm.yyyy
(day.month.year)
31.05.2004 hh:mm
(hours:
minutes)
15:56
am/pm mm/dd/yy
(day/month/year)
05/31/2004 hh:mm am/pm
(hours
:
minutes am/pm)
03:56 PM
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Device
Operating line
Range
Factory setting
Time format
24 hours / 12 hours
(am/pm)
24 hours
Main menu > Time of day / Date
Operating line
Range
Factory setting
Time of day
00:00…23:59 00:00
Date 01.01…31.12
01.01
Year 2000…2100
2000
The change from summertime to wintertime, and vice versa, is made automatically. The
date of the earliest changeover can be adjusted should the relevant regulations change.
The dates set for the change from wintertime to summertime, or from summertime to
wintertime, ensure that on the first Sunday after that date the time of day will change
from 02:00 (wintertime) to 03:00 (summertime), and from 03:00 (summertime) to 02:00
(wintertime).
If both dates are set to coincide, summer-/wintertime changeover will be inactive.
Main menu > Time of day / Date
Operating line
Range
Factory setting
Summertime start
01.01. … 31.12
25.03
Wintertime start
01.01. … 31.12
25.10
4.1.2 Communication
For the time of day, there are several sources available, depending on the master
clock. This can be entered on the controller. Time of day and date can be exchanged
via bus.
The following settings for clock time operation are possible:
•
Autonomous (does not send and does not receive)
•
Time of day
via
bus: Clock time slave (receives the synchronization signal via bus)
•
Time of day
on
the bus: Clock time master (sends the synchronization signal to the
bus)
Commissioning > Communication > Basic settings >
Time format
Setting
Summer-/wintertime
changeover
Setting
Setting