195/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
14 Fault tracing support
01.03.2005
Number
Name
Possible cause, remarks
306
[Boiler 6] boiler
sensor error
Error boiler sensor boiler 6
311
[Boiler 1] return
sensor error
Error return sensor boiler 1
312
[Boiler 2] return
sensor error
Error return sensor boiler 2
313
[Boiler 3] return
sensor error
Error return sensor boiler 3
314
[Boiler 4] return
sensor error
Error return sensor boiler 4
315
[Boiler 5] return
sensor error
Error return sensor boiler 5
316
[Boiler 6] return
sensor error
Error return sensor boiler 6
321
[B1] flue gas temp
sensor error
Error flue gas temperature sensor boiler 1
322
[B2] flue gas temp
sensor error
Error flue gas temperature sensor boiler 2
323
[B3] Flue gas temp
sensor error
Error flue gas temperature sensor boiler 3
324
[B4] flue gas temp
sensor error
Error flue gas temperature sensor boiler 4
325
[B5] flue gas temp
sensor error
Error flue gas temperature sensor boiler 5
326
[B6] flue gas temp
sensor error
Error flue gas temperature sensor boiler 6
330
Main flow sensor
error
Urgent message; must be acknowledged and
reset
331
Main return sensor
error
Nonurgent message; must be acknowledged, no
plant stop
332
[Boiler seq] MBRT
sensor error
Nonurgent message, must be acknowledged, no
plant stop
333
Consumer return
sensor error
Nonurgent message, must be acknowledged, no
plant stop
1210
[Twin pump 1] fault
Contacts D1and D2 are active.
Both fault inputs of the twin pump are active.
Rectify error.
Urgent message; must be acknowledged and
reset
1225
[Twin pump 2B]
overload
Contact D4 is active.
Nonurgent message; must be acknowledged
2201
Heat requisition mod
error
Error heat requisition DC 0…10 V.
Nonurgent message; must not be acknowledged,
no plant stop
2301
[B1 burner] no
checkback signal
Urgent, must be acknowledged, aggregate stop
of boiler 1
2302
[B2 burner] no
checkback signal
Urgent, must be acknowledged, aggregate stop
of boiler 2
2303
[B3 burner] no
checkback signal
Urgent, must be acknowledged, aggregate stop
of boiler 3
2304
[B4 burner] no
checkback signal
Urgent, must be acknowledged, aggregate stop
of boiler 4