23/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
3 Commissioning
01.03.2005
•
The first digit defines the type of hydraulic circuit of the boiler sequence
•
The second digit defines the type of burner or the type of burner control:
−
Kx.1: 1-stage burner
−
Kx.2: 2-stage burner
−
Kx.3: Modulating burner with 3-position control
•
For DC 0…10 V control of a modulating burner, the 1-stage burner is used as the
basic stage. In addition, a DC 0…10 V output must be assigned in the extra configu-
ration
•
The plant type always applies to a boiler sequence
−
with 2 boilers
−
and using the same type of burner
Additional boilers, other types of burner, a heating circuit or a primary controller can
be configured in the extra configuration.
•
The plant type activates function block “Boiler sequence manager“ and function
blocks “Boiler 1” and “Boiler 2”
K
Basic type K; no preconfigured inputs and outputs
K1.x
31
32
S
01
K2.x
31
32
S
04
M
M
K3.x
31
32
S
07
M
M
Types of hydraulic
circuits