Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
7 Boiler temperature control
01.03.2005
Number Text
Effect
2352
[K2 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 2
2353
[K3 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 3
2354
[K4 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 4
2355
[K5 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 5
2356
[K6 valve] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 6
Number Text
Effect
2361
[K1] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Not urgent, no boiler stop,
must be acknowledged and reset
2362
[K2] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Not urgent, no boiler stop,
must be acknowledged and reset
2363
[K3] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Not urgent, no boiler stop,
must be acknowledged and reset
2364
[K4] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state Not urgent, no boiler stop, must
be acknowledged and reset
2365
[K5] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Not urgent, no boiler stop,
must be acknowledged and reset
2366
[K6] flue gas overtem-
perature
Priority and effect can be parameterized.
Supply state: Not urgent, no boiler stop,
must be acknowledged and reset
Number Text
Effect
2401
[K1 pump] overload
Nonurgent message; must be acknowl-
edged and reset. No aggregate stop boiler 1
2402
[K2 pump] overload
Nonurgent message; must be acknowl-
edged and reset. No aggregate stop boiler 2
2403
[K3 pump] overload
Nonurgent message; must be acknowl-
edged and reset. No aggregate stop boiler 3
2404
[K4 pump] overload
Nonurgent message; must be acknowl-
edged and reset. No aggregate stop boiler 4
2405
[K5 pump] overload
Nonurgent message; must be acknowl-
edged and reset. No aggregate stop boiler 5
2406
[K6 pump] overload
Nonurgent message; must be acknowl-
edged and reset. No aggregate stop boiler 6
Number Text
Effect
2411
[K1 pump] no flow
Nonurgent message; must be acknowl-
edged and reset. No aggregate stop boiler 1
2412
[K2 pump] no flow
Nonurgent message; must be acknowl-
edged and reset. No aggregate stop boiler 2
2413
[K3 pump] no flow
Nonurgent message; must be acknowl-
edged and reset. No aggregate stop boiler 3
2414
[K4 pump] no flow
Nonurgent message; must be acknowl-
Flue gas temperature
limit exceeded
Overload
boiler pump
Flow fault
boiler pump