Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
9 Precontrol
01.03.2005
9.2 Configuration
Function block “Primary controller“ must always be activated in the extra configuration.
The function block is activated by assigning an output to a terminal.
Main menu > Commissioning > Extra configuration > Primary controller > Outputs
Operating line
Adjustable values / remarks
System pump
System pump B
Mixing valve 3-pos
Mixing valve modulating
Main menu > Commissioning > Extra configuration > Primary controller > Inputs
Operating line
Adjustable values / remarks
Flow sensor
Return sensor
[System pump] overload
[System pump B] overload
Flow signal pump
Heat requis modulating
Heat requisition 2-position
DHW requisition 2-pos
Frost prot requisition 2-pos
The heat requisitions can be sent to other devices via bus. In addition, there are 3 bi-
nary inputs and 1 analog input for transmitting heat requisitions.
9.2.1
Types of primary controllers
If only a pump or twin pump is configured, the primary controller consists of system
pump control. If, in addition, a mixing valve is configured, the primary controller consists
of mixing circuit control plus pump or twin pump control.
31
31
S
01
Y1
B1
M1
B7*
B7
31
31
S
02
B1*
M1
Primary controller type 1:
With mixing valve
Primary controller type 2:
With system pump
B1
Flow temperature sensor
B1* Flow temperature sensor (optional, for display only)
B7
Return temperature sensor (optional, for minimum limitation)
B7* Return temperature sensor (optional, for maximum limitation)
M1 System pump (can be a twin pump)
Y1 Mixing
valve
Primary controller type 1 with mixing circuit can provide optional minimum or maximum
limitation of the return temperature while primary controller type 2 only controls a sys-
tem pump depending on demand.
The flow or return temperature sensor of primary controller type 2 can be used for dis-
play purposes.
Basic configuration
Extra configuration
Outputs
Inputs
Heat requisition