10 Heating circuit control
01.03.2005
3131
S60
Solution:
Using the extra function “Room control combination”, 1 of the 2 heating circuits as the
master can preselect the operating mode for the second heating circuit, which is con-
figured as the slave.
If required, the setpoints can also be adopted by the master. This is accomplished with
configuration “Slave external setpoint“.
Problem:
A heating circuit covers the basic load and a ventilation plant covers the individual load
(heat demand) from the space.
In this application too, a common time switch or common preselected operating modes
may be desirable.
31
31
S
6
1
Combination of ventilation and heating
Solution:
Using the extra function “Room control combination”, the heating circuit can be oper-
ated as a slave whose room operating mode and time program are predefined by the
ventilation controller. It can be selected whether the setpoints for the heating circuit
shall be adopted externally (to be adjusted on the ventilation controller) or internally (to
be adjusted on the heating controller).
The heating circuit and ventilation must be assigned to the same geographical zone. A
room unit, if present, must also be assigned to the same geographical zone.
The ventilation controller
always
assumes the function of room control master.
A room unit, if present, always acts on the room control master.
During summer operation (heating circuit switched off via the heating limit), the ventila-
tion controller adopts the sustained mode.
Summer / winter operation changeover is ascertained via the heating limit (refer to
subsection 10.6.4 “Heating limit switch”) and sent to the ventilation controller via bus.
Example ventilation
and heating
⇒
Summer operation