124/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
7 Boiler temperature control
01.03.2005
Number Text
Effect
301
[Boiler 1] boiler sensor
error
Urgent message; must be acknowledged.
Aggregate stop boiler 1
302
[Boiler 2] boiler sensor
error
Urgent message; must be acknowledged.
Aggregate stop boiler 2
303
[Boiler 3] boiler sensor
error
Urgent message; must be acknowledged.
Aggregate stop boiler 3
304
[Boiler 4] boiler sensor
error
Urgent message; must be acknowledged.
Aggregate stop boiler 4
305
[Boiler 5] boiler sensor
error
Urgent message; must be acknowledged.
Aggregate stop boiler 5
306
[Boiler 6] boiler sensor
error
Urgent message; must be acknowledged.
Aggregate stop boiler 6
If the boiler temperature sensor is faulty, the burner will be shut down.
Number Text
Effect
311
[Boiler 1] return sensor
error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 1
312
[Boiler 2] return sensor
error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 2
313
[Boiler 3] return sensor
error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 3
314
[Boiler 4] return sensor
error
Nonurgent message; must be acknowl-
edged.
No aggregate stop boiler 4
315
[Boiler 5] return sensor
error
Nonurgent message; must be acknowl-
edged.
No aggregate stop boiler 5
316
[Boiler 6] return sensor
error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 6
In the case of plant with mixing valve for the maintained boiler return temperature, the
mixing valve will be driven to the fully closed position when there is no return tempera-
ture sensor and then deenergized to make possible manual adjustment.
Otherwise, the control behaves like a plant without return temperature sensor.
Number Text
Effect
321
[K1] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 1
322
[K2] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 2
323
[K3] Flue gas temp sen-
sor error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 3
324
[K4] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 4
325
[K5] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 5
326
[K6] flue gas temp sensor
error
Nonurgent message; must be acknowl-
edged. No aggregate stop boiler 6
Number Text
Effect
2301
[K1 burner] fault
Urgent message; must be acknowledged.
Aggregate stop boiler 1
2302
[K2 burner] fault
Urgent message; must be acknowledged.
Aggregate stop boiler 2
Error boiler tempera-
ture sensor
Error return tempera-
ture sensor
Error flue gas
temperature sensor
Fault burner