143/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
9 Precontrol
01.03.2005
Setting “System pump locking signal = Off“ means that the system pump shall also
respond to locking signals.
Main menu > Settings > Primary controller > Limitations
Operating line
Range
Factory setting
Flow temperature max
0…140 °C
140 °C
Flow temperature min
---- / 0…140 °C
---- °C
Flow temperature rise max
---- / 1…600 K/h
---- K/h
Return temp min*
---- / 0…140 °C
---- °C
Return temp max*
---- / 0…140 °C
---- °C
Frost protection for the plant
Off / On
On
* Displayed or hidden, depending on the type of limitation
9.8.3
Pump overrun and mixing valve overrun
To protect the boiler against overtemperatures after the burner has shut down (when
there are no more active heat consumers), an overrun time for the consumers can be
set on the boiler controller.
After the burner has shut down, the overrun time ensures that the heating circuits and
DHW heating will still draw heat for that period of time provided they were consuming
heat up to 1 minute before the burner was shut down. In any case, pumps and mixing
valves have an overrun time of 60 seconds.
With primary controller type 1, the mixing valve maintains the former setpoint during the
overrun time and the pump runs; with primary controller type 2, only the pump runs during
that period of time.
9.8.4
Pump kick and valve kick
The pump kick is a protective function that is carried out periodically. It prevents pumps
and / or mixing valves from seizing after longer off periods.
For more detailed information, refer to section 5.5 “Pump kick and valve kick”.
9.9 Error
handling
When commissioning is completed (commissioning menu quit), the system checks
whether the configured sensors have been connected. In the event of an open-circuit or
short-circuit, an error message will be delivered.
Number Text
Effect
57
Prim controller error flow
sensor
Nonurgent message; must be acknowl-
edged
In the case of an error of the flow temperature sensor, the mixing valve will be driven to
the fully closed position to become inactive (3-position actuator), so that it can be
manually operated.
Number Text
Effect
58
Prim controller error ret
sensor
Nonurgent message; must be acknowledged
The primary controller behaves as if no return temperature sensor was used. Limitation
of the return temperature is inactive.
System pump and
locking signals
Settings
Error handling
Errors of sensors
Sensor error return
temperature