14 Fault tracing support
01.03.2005
14.2 Rectification of errors
Question Reply
E.g., error message “[HC 1]
error flow sensor“ appears al-
though a sensor is connected.
Check to see if, in addition, error “Fault extension
module“ occurred. This error can lead to the
display of subsequential errors.
When commissioning the plant,
the wrong language was se-
lected.
How do I find “my” language?
1. Press the ESC button and the OK knob simul-
taneously.
2. Choose the password level and enter number
112
as the password (same as international
emergency call) and confirm by pressing the
OK knob. The language changes to English.
3. Select your language from the ”
Settings > Device
> Language
” menu
The device is completely
switched off, “Operation locked,
Remote operation" appears.
How do I start the device again?
Remote operation (OCI700.1) set the device to
commissioning mode, which has locked local
operation.
If the device is not corrected restarted via remote
operation, it maintains this state. Locally, the
device can only be restarted by briefly discon-
necting the power supply
The buttons on the QAW740
room unit do not work.
A: The “Geographical zone“ of controller and
room unit must agree.
B: On the controller, the room operating mode is
overridden by a function of higher priority.
For more detailed information, refer to subsec-
tion 10.5.5 “Control priorities in the heating cir-
cuit”