152/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
01.03.2005
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit > Space heating
Operating line
Range
Factory setting
Timer function*
0…720 min
60 min
* This setting does not apply to the QAW740 room unit; in that case, the setting is made directly on the room
unit
The activated timer can be stopped by changing the room operating mode (e.g. via the
room operating mode selector).
10.4.7 Room control combination
The heating circuit of the RMK770 can be combined with a heating circuit of some other
controller. This combination of 2 room control systems is required, for example, when 1
heating circuit is used for the underfloor heating system and 1 for the radiators. Another
example is the combination of ventilation and heating in a room (e.g. in a hall).
If only the time program shall be jointly used, this can be done without a room control
combination. In that case, the time switch of the heating circuit is to be operated as the
master or slave. For more detailed information, refer to section 5.1 “Time switch”.
In the event of a power failure, the operating mode of the slave is on Comfort
until the
master sends another signal via bus.
For more detailed information about ventilation, refer to the Basic Documentation on the
RMU7… (P3140).
Main menu > Commissioning > Extra configuration > Heating circuit > Functions
Operating line
Range
Factory setting
Room control combination
Master / Slave external
setpoint / Slave internal
setpoint
Master
There are no settings required.
The room operating mode selector and the setpoints (if external) must be set on the
master.
Main menu > Commissioning > Communication > Room heating circuit
Operating line
Range
Factory setting
Geographical zone (apartment)
1…126 1
Communication is described in chapter 13 ”Communication”.
Problem:
The basic load is covered by a heating circuit with weather-compensated control and
the load-dependent part by a second heating circuit with or without room influence. The
2 heating circuits shall operate in parallel and be controlled by a common switching
program or a room operating mode selector.
Settings
Tip
Note
Behavior after a
power failure
Extra configuration
Settings
Communication
Example with
2 heating circuits