138/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
9 Precontrol
01.03.2005
Main menu > Settings > Primary controller > Mixing circuit controller
Operating line
Range
Factory setting
[Tn] return temp limitation max
0…60 min
30 min
If the return temperature falls below the limit value, the primary controller’s flow tem-
perature setpoint will be lowered. When the return temperature returns to a level above
the limit value, the lowering of the flow temperature setpoint will be gradually reduced.
Limitation operates as an I-controller. The integral action time is entered as a fixed
value.
9.3
Text designation of the primary controller
Main menu > Settings > Primary controller
Operating line
Range
Factory setting
Primary controller
Text A…Z
Primary control-
ler
If required, specific text can be assigned to the primary controller. This text will then
appear on the menu and on the info display.
9.4 Plant
operation
Plant operation indicates whether the primary controller is switched on and whether the
pump runs.
Main menu > Primary controller > Plant operation
Operating line
Range
Factory setting
Preselection
Auto / Off*
Auto
State
Off / On
Cause
Commissioning /
Requisition /
Frost protection for consumer /
Frost protection for the flow /
Frost protection for the plant /
Overtemp protection/overrun /
Plant operation selector /
No requisition
* Frost protection functions are ensured
For service purposes, the primary controller can be switched off. In that case, the valve
will be closed and the pump switched off, or valve and pump start their overrun.
The heat demand is not passed on when in the “Off” position!
When preselecting “Off”, the internal frost protection function will remain active and frost
protection-related heat requisitions (frost protection for the flow) from externally will be
accepted and handled.
When service work is completed, the selector must be set back to “Auto”.
The display shows the primary controller’s current state (On / Off).
It is indicated why the current state is active.
Minimum limitation of
the return temperature
Plant operation
Preselection (plant opera-
tion selector)
⇒
State
Cause