Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
6 Boiler sequence management
01.03.2005
Number Text
Effect
2491
[Main pump] overload
Nonurgent message; must be acknowl-
edged and reset
2492
[Main pump B] overload
Nonurgent message; must be acknowl-
edged and reset
2493
[Main pump] no flow
Nonurgent message; must be acknowl-
edged and reset
2494
[Main pump B] no flow
Nonurgent message; must be acknowl-
edged and reset
2495
[Main pump] fault
Urgent message; must be acknowledged
and reset, plant stop
Number Text
Effect
2391
[Boiler seq] water shortage
Can be parameterized
2392
[Boiler sequence] over-
pressure
Can be parameterized
2393
[Boiler sequence] under-
pressure
Can be parameterized
Number Text
Effect
2396
Main flow temp not reached Not urgent, must be acknowledged, no
plant stop
Number Text
Effect
332
[Boiler seq] MBRT sensor
error
Nonurgent message; must be acknowl-
edged, no plant stop
333 Consumer
return
sensor
error
Nonurgent message; must be acknowl-
edged, no plant stop
Number Text
Effect
5593
Number of boilers wrong
setting
Nonurgent message; must be acknowl-
edged
5594
Invalid lead boiler
Nonurgent message; must not be ac-
knowledged
2201
Heat requisition mod error
Nonurgent message; must not be ac-
knowledged, no plant stop
5591 Failure
boiler
sequence
manager
Nonurgent message; no plant stop; must
be acknowledged
5592
>1 boiler sequence man-
ager
Nonurgent message; no plant stop; must
be acknowledged
Error main pump
Fault supervision
boiler sequence
Main flow temperature
supervision
Sensor supervision
general
Various errors