45/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
3 Commissioning
01.03.2005
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > …
Operating line
Range
Factory setting
Value low
Depending on the se-
lected type
Depending on
the type
Value high
Depending on the se-
lected type
Depending on
the type
Flow temperature with an active signal of DC 0…10 V = 0…100 °C:
Low limit value:
0 °C
High limit value:
100 °C
With a passive temperature sensor, the measured value can be readjusted by
−
3.0 to
+3.0 K to compensate for line resistance. It is thus possible to make onsite calibrations
with a reference instrument.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > RMK770.X…
Operating line
Range
Factory setting
Correction
−
3.0…
+
3.0 K
0 K
When the "Commissioning" menu is quit, a check is made to see which sensors are
connected. If, later, one of the sensors connected at this point in time is missing, or if
there is a short-circuit, a fault status message "[…X…] sensor error" will be delivered.
If there is an open-circuit of the measuring line, the operator unit displays the measured
value as: ----.
A short-circuit is displayed as: oooo.
The digital inputs can accept signals from potential-free contacts for control functions.
Main menu > Commissioning > Extra configuration > Miscellaneous > Input identifier
Operating line
Setting
N.X5 Digital
The normal position can be predefined for each digital input.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs
Operating line
Range
Factory setting
Normal position
Open / Closed
Open
G
G
G0
X...
G0
N
31
40
A
0
5
A
C
24 V
M
F...
∆
p
X...
M
F...
Digital signals cannot be monitored.
Setting
Example
Measured value
correction
Setting
Error handling
Digital inputs
Configuration of input
Normal position
Setting
Error handling