6 Boiler sequence management
01.03.2005
The other sensors which also belong to function block “Boiler sequence manager“, such
as the return sensor for the common maintained boiler return temperature, or the return
sensor for the consumers, are monitored for short-circuit and open-circuit.
Number Text
Effect
332
[Boiler seq] MBRT sensor
error
Nonurgent message, must be acknowl-
edged, no plant stop
333 Consumer
return
sensor
error
Nonurgent message, must be acknowl-
edged, no plant stop
6.5
Heat demand and heat requisition
MAX
31
32
Z
11
Heat requisition 2-position
Heat requisition continuous (DC 0…10 V)
Heat requisition heating circuits
Heat requisition DHW heating
Heat requisition precontrol
(heating, ventilation, individual room control)
Heat requisition DHW
Heat requisition frost
Setpoint preselection manual
Setpoint sustained mode
Function block “Boiler sequence manager“ collects the heat demand from all consum-
ers (heating circuit, DHW heating and primary controller), the external inputs and the
manual setpoint preselection. These setpoints are used to generate the maximum
value.
or
Main menu > Boiler sequence manager > Boiler sequence optg mode
Operating line
Range
Factory setting
Setp preselection manual
---- / 8…140 °C
---- °C
If there is no heat requisition, sustained mode can become active, if parameterized.
On the controller, 1 analog and a maximum of 3 digital inputs can be configured as heat
demand inputs.
Main menu > Commissioning > Extra configuration > Boiler sequence manager > Inputs
Operating line
Adjustable values / remarks
Heat requis modulating
Heat requisition 2-position
DHW requisition 2-pos
Frost prot requisition 2-pos
The three 2-position heat requisitions differ in the type of heat requisition.
Depending on the selection of the boiler sequence operating mode (
… > Main menu >
Boiler sequence manager > Boiler sequence optg mode > Preselection
) either all 3 types are
evaluated or only individual ones.
Boiler sequence optg mode
Off
Only the frost input is considered
Release DHW
Generation of maximum value from the DHW and frost
inputs
Auto
Generation of maximum value from all 3 inputs
Sensor supervision in
general
Error messages