Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
01.03.2005
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit > Optimizations/influences
Operating line
Range
Factory setting
Room influence
---- (none) / 0…10
----
31
31
B
20
TOeff
+
-
SpTR
TR
20 °C
SpTFlDe
SpTFlHi
SpTRN
TFl
TOeff
TODe
TOHi
+
-
+
-
+
+
TFl
SpTR
TR × V
-
Due to the room temperature deviation
∆
TV, the change of flow temperature setpoint
corresponds roughly to the value of:
∆
TFl=
∆
TR × V × (sHc + 1)
∆
TFl Flow temperature setpoint change
sHc Heating curve slope
∆
TR Room temperature setpoint change
Sp
Setpoint
V
Room influence
TRx Room temperature
During boost heating, the room temperature setpoint boost also produces an increase
of the flow temperature setpoint. In that case, the greatest of the 2 values is used for
generating the setpoint.
31
31
B
22
SpTR
TR
+
-
TR
TR × V
-
TRBoost
MAX
TReff
The resulting room temperature setpoint has a minimum limitation of 5 °C and a maxi-
mum limitation of 35 °C.
10.6.4 Heating limit switch
The heating limit switch can restrict the amount of heat delivered to the heating circuit.
This prevents the waste of heating energy at higher outside temperatures.
To determine the heating limit, the following outside temperature values are taken into
consideration (refer to subsection 10.6.1 “The composite and the attenuated outside
temperature”):
•
The current outside temperature TO
•
The composite outside temperature TOeff
•
The attenuated outside temperature TOstrDmp
•
When
all 3
temperatures lie 1 °C
below
the Comfort heating limit, heat will be re-
leased in Comfort and Precomfort mode.
•
When
1 of the 3
temperatures lies
above
the Comfort heating limit, the delivery of
heat will be locked
If a change was made to “Continuously Comfort”, the heating limit function is inactive,
which means that continuous heating is provided in accordance with the heating curve.
Exempted from this is the room control combination with an RMU7… ventilation controller.
Settings
Rule of thumb
Comfort heating limit
⇒