125/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
7 Boiler temperature control
01.03.2005
Number Text
Effect
2303
[K3 burner] fault
Urgent message; must be acknowledged.
Aggregate stop boiler 3
2304
[K4 burner] fault
Urgent message; must be acknowledged.
Aggregate stop boiler 4
2305
[K5 burner] fault
Urgent message; must be acknowledged.
Aggregate stop boiler 5
2306
[K6 burner] fault
Urgent message; must be acknowledged.
Aggregate stop boiler 6
Number Text
Effect
2311
[K1 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 1
2312
[K2 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 2
2313
[K3 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 3
2314
[K4 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 4
2315
[K5 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 5
2316
[K6 burner] no checkback
signal
Urgent message; must be acknowledged
and reset. Aggregate stop boiler 6
Number Text
Effect
2321
[Boiler 1] water shortage
Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2322
[Boiler 2] water shortage
Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2323
[Boiler 3] water shortage
Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2324
[Boiler 4] water shortage
Priority, effect and acknowledgement can be
parameterized.
Supply state Urgent, boiler stop, must be
acknowledged
2325
[Boiler 5] water shortage
Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
2326
[Boiler 6] water shortage
Priority, effect and acknowledgement can be
parameterized.
Supply state: Urgent, boiler stop, must be
acknowledged
Number Text
Effect
2331
[Boiler 1] overpressure
Priority, effect and acknowledgement can be
parameterized.
Error burner operation
supervision
Fault 1
(water shortage)
Fault 2 (overpressure)