6 Boiler sequence management
01.03.2005
Heat demand can be predefined with a DC 0…10 V signal.
The signal can be matched to the DC 0…10 V signal source:
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > Heat requisition boiler sequence
Operating line
Range
Factory setting
[Modulating] setpoint at 0 V
–150…50 °C
0 °C
[Modulating] setpoint at 10 V
50…500 °C
100 °C
[Modulating] limit value
0…140 °C
10 °C
DC 0...10 V
0
2
4
6
8
10
-20
0
20
40
60
80
100
120
°C
2
3
313
1D14
c
Value in °C at DC 0 V
d
Value in °C at DC 10 V
e
Limit value for heat demand (temperatures below this level are interpreted as “no heat demand”)
With the binary input, heat demand can be predefined in the form of a fixed value.
The “Inputs“ menu can be used to parameterize whether the input shall be activated
with a closed or open contact.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > RMK770…
or
RMZ78…
Operating line
Range
Factory setting
Normal position
Open / Closed
Open
Setting “Normal position = Open” means that a closed contact identifies a heat requisi-
tion.
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Inputs > Heat requisition Heat requisition boiler sequence
Operating line
Range
Factory setting
[2-pos] setpoint normal
0…140 °C
70 °C
With the binary input, it is also possible to predefine a fixed value as a heat demand,
which maximum value generation interprets like a heat requisition of the DHW or frost
type.
Depending on the boiler sequence operating mode (see above), only 1 requisition of
the DHW type and / or frost type is considered.
Main menu > Commissioning > Settings > …
or
Main menu > Main menu > Settings > Inputs > Heat requisition boiler sequence
Operating line
Range Factory
setting
[2-pos] setpoint DHW
0…140 °C
70 °C
[2-pos] setpoint frost prot
0…140 °C
70 °C
Heat requisition
modulating
Heat requisition 2-
position
Heat requisition 2-
position [DHW or frost
protection]