172/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
01.03.2005
10.12 Diagnostic choices
Main menu > Heating circuit > Inputs/setpoints
Operating line
Adjustable values / remarks
Composite outside temp
…°C
Attenuated outside temp
…°C
Actual value flow temp
…°C
Flow temperature setpoint
According to section 10.7 “Mixing valve
control” (load control considered)
Room sensor temp.
…°C
Actual value room temp
…°C
[Room temperature 1] bus
…°C
[Room temperature 2] bus
…°C
Room temperature model value
Current room temp setpoint
…°C; according to user’s preselection, cur-
rent room operating mode and interventions
Room setpoint absolute
…°C
Room setpoint relative
…°C
Actual value return temp
…°C
Return temperature max
…°C
Return temperature min
…°C
Room operating mode
Timer function
[Heating circuit pump] overload
0 / 1 (1 = overload)
[Heating circuit pump B] overload
0 / 1 (1 = overload)
Flow signal pump
Main menu > Heating circuit > Outputs
Operating line
Adjustable values / remarks
Heating circuit pump
Off / On
Heating circuit pump B
Off / On
Mixing valve 3-pos
0…100 %
Mixing valve modulating
Closing / ---- / Opening
Main menu > Heating circuit > Limitations
Operating line
Adjustable values / remarks
Flow temperature max
Off / On
Flow temperature min
Off / On
Flow temperature rise
Off / On
Return temperature min
Off / On
Return temperature max
Off / On
Inputs/setpoints
Outputs
Limitations