11 Function block miscellaneous
01.03.2005
Number Text
Effect
10 Outside
temp
sensor error
Nonurgent message; must not be acknowledged
11
>1 outside tem-
perature sensor
Urgent message; must be acknowledged
12
Outs sensor simu-
lation active
Nonurgent message; must not be acknowledged
11.4 Display
inputs
On the RMK770, 4 universal inputs can be defined for display purposes.
Main menu > Commissioning > Extra configuration > Miscellaneous > Inputs
Operating line
Adjustable values / remarks
Display input 1
Assign terminal
Display input 2
Assign terminal
Display input 3
Assign terminal
Display input 4
Assign terminal
The type or unit of the display input can be selected with the input identifier.
Main menu > Commissioning > Extra configuration > Miscellaneous > Input identifier
Operating line
Range
Factory setting
Display input 1
°C / % / g/kg / kJ/kg /
W/m2 / m/s / bar / mbar
/ Pa / ppm / Universal
000.0 / Universal 0000 /
Digital
°C
Display input 2
Like display input 1
°C
Display input 3
Like display input 1
°C
Display input 4
Like display input 1
°C
For detailed information about resolution, type of sensor, etc., refer to subsection 3.4.8
“Configuration of the universal inputs and outputs”.
The type of input can be selected. In the case of an analog input, it is the type of input,
and in the case of a digital input, the normal position.
Main menu > Commissioning > Settings > Inputs > …X…
Operating line
Range
Factory setting
Type reference
Ni1000 / 2×Ni1000 / T1
/ Pt1000 / 0…10 V
Ni1000
Value low
Value high
Correction
Normal position
Open / Closed
Open
The inputs can be assigned free text (maximum 20 characters).
Main menu > Commissioning > Settings > Texts
Operating line
Range
Factory setting
Display input 1
A…Z, a…z, 0…9, vari-
ous punctuation marks,
various special charac-
ters
Display input 2
Like display input 1
Display input 3
Like display input 1
Fault status messages