164/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
10 Heating circuit control
01.03.2005
•
When
all 3
temperatures lie 1 °C
below
the Economy heating limit, heat will be re-
leased in Economy and Protection mode
•
When
1 of the 3
temperatures lies
above
the Economy heating limit, delivery of heat
will be locked
HDCmf
HDEco
TOact
TOStrDmp.
TOeff
31
31
D
3
0
Cmf
heating
limit
Eco
heating
limit
Main menu > Settings > Heating circuit > Space heating
Operating line
Range
Factory setting
Comfort heating limit
--- (none) / –5…25 °C
17 °C
Economy heating limit
--- (none) / –5…25 °C
5 °C
The following applies:
•
If the Comfort heating limit is set to --- (none), there is a heating limit only in Econ-
omy and Protection mode. There will be no changeover to summer operation
•
If the Economy heating limit is set to --- (none), the Comfort heating limit acts in
Economy
and Protection mode
For operation in combination with the ventilation controller, summer / winter operation
changeover is used as an overriding function.
When the attenuated outside temperature exceeds the Comfort heating limit, a change
to summer operation will be made; this also applies to “Continuously Comfort
”
.
10.7 Mixing valve control
10.7.1 Control
The flow temperature setpoint determined by weather-compensated heating circuit
control produces the effective setpoint for mixing valve control while giving considera-
tion to load control.
Mixing valve control can be accomplished with a 3-position mixing valve or a mixing
valve using DC 0…10 V control. The type of actuator is selected in the extra configura-
tion.
The following mixing valve settings apply to both the 3-position mixing valve and the
DC 0…10 V actuator:
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Heating circuit > Controller
Operating line
Range
Factory setting
Actuator running time
1…600 s
120 s
P-band Xp
1…100 K
48 K
Integral action time Tn
0…600 s
10 s
For more detailed information about mixing valve control and its setting aids, refer to
section 5.7 “Mixing valve control”.
Economy heating limit
Settings
Summer / winter operation
(information for ventilation)
Setpoint
3-position / DC 0…10 V
actuator