196/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
14 Fault tracing support
01.03.2005
Number
Name
Possible cause, remarks
2305
[B5 burner] no
checkback signal
Urgent, must be acknowledged, aggregate stop
of boiler 5
2306
[B6 burner] no
checkback signal
Urgent, must be acknowledged, aggregate stop
of boiler 6
2311
[B1 burner] no
checkback signal
Urgent, must be acknowledged and reset, aggre-
gate stop of boiler 1
2312
[B2 burner] no
checkback signal
Urgent, must be acknowledged and reset, aggre-
gate stop of boiler 2
2313
[B3 burner] no
checkback signal
Urgent, must be acknowledged and reset, aggre-
gate stop of boiler 3
2314
[B4 burner] no
checkback signal
Urgent, must be acknowledged and reset, aggre-
gate stop of boiler 4
2315
[B5 burner] no
checkback signal
Urgent, must be acknowledged and reset, aggre-
gate stop of boiler 5
2316
[B6 burner] no
checkback signal
Urgent, must be acknowledged and reset, aggre-
gate stop of boiler 6
2321
[Boiler 1] water
shortage
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2322
[Boiler 2] water
shortage
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2323
[Boiler 3] water
shortage
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2324
[Boiler 4] water
shortage
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2325
[Boiler 5] water
shortage
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2326
[Boiler 6] water
shortage
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2331
[Boiler 1] overpres-
sure
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2332
[Boiler 2] overpres-
sure
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2333
[Boiler 3] overpres-
sure
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2334
[Boiler 4] overpres-
sure
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2335
[Boiler 5] overpres-
sure
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)
2336
[Boiler 6] overpres-
sure
Priority, effect and acknowledgement can be
parameterized (default: urgent, boiler stop, must
be acknowledged)