5 General functions, fundamentals
01.03.2005
5.1.4 Error
handling
For each "Geographical zone", only one time switch master may be used. If several
controllers are parameterized as the master, a fault status message will be delivered.
The message is sent by the controller which receives 2 time switch signals.
Number Text
Effect
5102
>1 time switch in
plant 1
Nonurgent message; must be acknowledged
If the controller expects a time switch signal via bus and the signal is not sent, a fault
status message "System time switch failure" will be delivered. It is ready set to Comfort
mode.
Number Text
Effect
5101 Syst
time
switch
failure plant 1
Nonurgent message; must not be acknowledged
5.2
Holidays/special days
Days deviating from the normal 7-day program can be entered by the plant operator as
holidays or special days, using the "Holidays/special days" menu. Entry is described in
Operating Instructions B3131.
For each RMK770, a holidays/special days program is available. Separate settings
make it possible to select the operating mode that shall apply to both the heating cir-
cuits and DHW heating during holidays.
The “Holidays/special days” function is only active if the room operating mode or the
DHW Auto mode has been selected for the heating circuit(s) and / or DHW heating.
The RMK770 does not provide DHW heating, but DHW signals from the Konnex bus
can have an impact.
5.2.1 Communication
If the controller is connected to other controllers via bus, the holidays/special days
program can be made available to other controllers (master), or it can be adopted from
some other controller (slave).
The following combinations are possible:
Entry Effect
Diagram
Autono-
mous
The holidays/special days program only acts
locally on this controller.
The holidays/special days program has no
impact on the holidays/special day zone en-
tered under communication.
Slave
The holidays/special days program in this
controller is not active.
The program acting is the external holi-
days/special days program that has the same
holidays/special day zone set. The external
holidays/special days program must be set as
the master holidays/special days program
Fault status messages
Fault status messages
Note on Holidays/special
days
Note on DHW heating