89/226
Building Technologies
Boiler Sequence Controller RMK770
CE1P3132en
HVAC Products
6 Boiler sequence management
01.03.2005
If the boilers cannot modulate at a sufficiently low level, the main flow temperature will
rise until a boiler is switched off via the temperature-time integral.
6.4
Supervision of faults
The main pump (main twin pump) can be monitored with an overload input each and /
or a flow switch each (
… Extra configuration > Boiler sequence manager > Inputs).
The parameters for the pump or twin pump fault inputs are fixed and cannot be
changed.
The fault status signal delay for the flow switch is 60 seconds.
The setting parameters for the main twin pump can be found on menu
… Settings > Boiler
sequence manager > Twin pump
. For more detailed information about the functionality of
the twin pump, refer to chapter 5 “General functions, fundamentals”.
Number Text
Effect
2491
[Main pump] overload
Nonurgent message; must be acknowledged
and reset
2492
[Main pump B] overload
Nonurgent message; must be acknowledged
and reset
2493
[Main pump] no flow
Nonurgent message; must be acknowledged
and reset
2494
[Main pump B] no flow
Nonurgent message; must be acknowledged
and reset
2495
[Main pump] fault
Urgent message; must be acknowledged
and reset, plant stop
For fault supervision of the boiler sequence, there are 3 binary fault inputs available.
These are freely configurable, whereby the 3 fault outputs use the following factory
settings:
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler sequence manager > Fault settings > Fault input 1
Operating line
Range
Factory setting
Fault text
A…Z
Water shortage
Impact of fault
Stop / No stop
Stop
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority
Urgent / Not urgent
Urgent
Fault status signal delay
00.00…59.55 m.s
(minutes.seconds)
00.05 m.s
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Boiler sequence manager > Fault settings > Fault input 2
Operating line
Range
Factory setting
Fault text
A…Z
Overpressure
Impact of fault
Stop / No stop
Stop
Fault acknowledgement
None / Acknowledge /
Acknowledge and reset
Acknowledge
Fault priority
Urgent / Not urgent
Urgent
Fault status signal delay
00.00…59.55 m.s
00.05 m.s
Note
Supervision of
main pump
Error messages
Fault supervision of
boiler sequence